The Science Behind Steam Assisted Flares
Flares are a common site in petrochemical plants.
Due to the nature of flares being a safe way of disposing of large quantities of product when there is a problem, the load on a flare can change from a low flow to a high flow rather quickly. While this will be a scheduled event at times (like during a scheduled outage), it will often be the result of an upset condition. Regardless of the situation, the system has to be designed to handle the entire flow range.
While this system is an integral part of operating the plant safely, steam assisted flares often do not get the attention they deserve. Steam is used at the flare to aspirate air into the combustion zone, shape the flame of the flare, cool the tip of the flare, and reduce noise.
While steam can be fed to three parts of the flare (center steam, upper rim, and inside tubes), they are typically regulated through a single control valve. Each part can impact the performance and reliability of the system. For optimum performance, controlling the flow of steam to the flare and supplying high quality (dry) steam is needed.
Flare Control
If too much steam is allowed to flow to the flare, there are several detrimental things that can happen. The collision above the flare tip can create a zone of higher pressure that can force the flame back down into the plenum. This internal burning can cause structural damage to the flare. Combustion efficiency which in this case, the destruction of hydrocarbons can actually be decreased by too much steam flow. Additionally, feeding too much steam to the flare is a waste of energy.
If too little steam is supplied to the flare, smoking (primarily the presence of carbon) will occur. This can be indicative of poor combustion, although smoking can occur while there is acceptable combustion efficiency. Unfortunately, smoking is something that can cause public concern around a plant and is best avoided.
Steam Flare Solutions
Poor quality steam and/or improper steam mains drainage can hamper or even destroy the best flare design. Steam quality refers to the amount of moisture that is entrained in the steam flow. This is commonly called out with a dryness fraction that is represented as a percentage. For example, 100% quality steam has no entrained moisture whereas 90% quality steam contains 10% moisture by mass.
This entrained moisture can cause erosion in the steam ring at the top of the flare as well as the nozzles that are designed to create target velocities for the induction of air and proper combustion mixture.
To address the steam quality, a separator is recommended to be installed upstream of the steam supply control valve. Unlike a drip trap, the steam trap installed off the separator needs to be sized to handle the amount of condensate that could be knocked out of the steam flow at the maximum load. Typically, for saturated steam, we would recommend a design load of 10% of the maximum steam flow. This would account for 90% quality steam being supplied to the separator.
Condensate Collecting
There are multiple points where condensate can accumulate in the piping feeding a steam assisted flare. If condensate is blown to the top of the flare, it can damage the rings and/or nozzles that are part of the flare system. The most serious consequence of note is typically having the pilot or flame extinguished. This can allow toxic hydrocarbons or pollutants to be discharged to atmosphere. The costs associated with this event can be high.
At a minimum, there needs to be a properly designed drip leg and properly sized drip trap upstream of the steam supply valve. On the high-pressure side (upstream) of the valve, this trap can be tied into a condensate return line since there should always be a supply pressure.
Proper Drainage
This is where many plants make a mistake. Ideally, flaring should happen only for short periods of time. A fixed bleed should allow a small flow of steam into the steam supply piping to keep it hot (as shown in small bypass line in graphic Fig 2). This will minimize the amount of steam that will condense when the steam supply valve needs to open.
Normally, there will be little or no pressure downstream of the steam supply valve due to the valve being closed. The steam flowing through the orifice in the bypass to keep the steam supply hot will condense and that condensate will accumulate in any low or horizontal runs in the piping. A drip trap (ideally a float and thermostatic trap) should be installed at all low points and must flow down into an atmospheric return on the low pressure (downstream) side of the steam supply valve. A common mistake is to tie the steam trap outlet into a condensate return line. Any backpressure can keep this part of the system from draining properly.
If the condensate is to be returned from low points downstream of the steam supply control valve, then the traps should discharge to a vented receiver (with an overflow connection) that drains into a condensate return pump.
Just as the process piping and controls for a flare need to be properly designed to handle the full range of product flow rates to the flare, the steam being supplied to the flare requires equal consideration. Keeping the system properly drained is paramount and will impact the performance and reliability of the steam assisted flare.
Mike Mabry is area manager for Oil & Gas and Chemicals at Spirax Sarco.
This article originally appeared in Steam News Magazine, Vol 6, No 3.
RELATED CONTENT
-
The Different Types of Solenoid Valves and How They Work
Solenoid valves are automatic flow control devices popular across different industrial applications.
-
Valve Basics: Electric Actuator Controls
Electric valve actuators control the opening and closing of valves. With a motor drive that provides torque to operate the valve, these actuators are frequently used on multi-turn valves such as gate or globe and also on ball, plug and other quarter-turn valves.
-
Proper Care of Knife Gate and Slurry Valves
How to resolve—and avoid—field failures of knife gate and slurry valves