Solenoid Valves

Solenoid valves are usually considered an accessory in the process valve industry; however, while there is some truth to this, these accessories are crucial to the proper operation of any system that uses them.
#basics #automation

Share

The solenoid valve has many features that need to be considered when creating a specification. Eight specification points should be addressed to correctly choose the right solenoid valve for an application. These specification points are:

  • Type
  • Operation
  • Media
  • Size
  • Pressure
  • Atmosphere
  • Voltage
  • Extras

More information on these eight points is included in this article.


TYPE

Three-way valves (Figure 2) are those that have three ports-a pressure or inlet port (port 1), a cylinder port (port 2) and an exhaust port (port 3). A 3-way valve’s most common application is for process valve automation. The solenoid valve sends air to a spring return actuator or cylinder, which creates rotational or linear movement to open or close a process valve. In this case, the media is usually compressed air or gas that is creating work, which is where the term “fluid power” is derived. The power of a compressed gas or pressurized liquid is controlled to create mechanical work. Three-way valves are usually referred to as 3/2 valves-they have three ports and two positions.

  • In cases where the valve is de-energized or off: The pressure port to cylinder port 2 is open while cylinder port 4 to exhaust is open.
  • In cases where the valve is energized or on: The pressure port to cylinder port 4 is open while cylinder port 2 to the exhaust is open.

Since the actuator or cylinder does not have a spring on one side, it must rely on fluid power from a 4-way valve to open and close. Four-way valves can be referred to as 4/2 or 5/2 valves, and they can have four or five ports and two positions.

There are other configurations such as the dual solenoid, fail-in-last-position, 3/3, and 5/3 solenoid valves, but explanations are best left for another article.



OPERATION

Operation is a word used to describe if a valve is normally open (NO), normally closed (NC) or universal (U). NO and NC refers to the state of a 2-way solenoid valve when de-energized or off. NO, NC or U is used to describe the state of a 3-way valve when it is de-energized or off. Below is a table that describes operation modes of 2-way and 3-way valves.



MEDIA

Media are the types of fluid that flow through the valve. Typical solenoid valve media are air, inert gas, fuel gas, water, oil and steam. Media are a very important consideration in solenoid valve specification because the materials of the valve must be compatible with the media. If the valve internal materials are not considered, internal corrosion can take place.

Media temperature also is an important consideration, and in selecting the right valves, it is useful to know what minimum and maximum media temperatures are. High temperature media such as steam can have adverse effects on the valve's coil temperature rise.

Regardless of what the media are, however, the valves need to be clean and free from debris left from piping installations. When using a valve with a gas media, such as compressed air, installing a filter before the inlet of the valve is recommended. When using a valve with liquid media, a strainer is recommended. In all cases, installers should check with the manufacturer for recommended filtration values, which should vary depending on the specific solenoid valve used.


SIZE


PRESSURE

Pressure rating of a valve is the maximum differential pressure applied into the pressure or inlet port when the valve orifice is closed that the valve can withstand without significant leakage. But there’s more to the situation than that. This maximum pressure is usually tested at the valve's minimum-rated temperature and the valve’s maximum-rated temperature for a large number of cycles. This is another point of inconsistency in the valve manufacturing world. Not every maker pressure-rates solenoid valves the same way. If the valve has third-party approval, there is consistency; however, if there is not a requirement for third-party approval such as UL, not all valves are equal.

The main differences between manufacturers' pressure ratings are factors of safety. If maximum pressure is a crucial specification point, those specifying should check with the manufacturers to see how they rate their products. Be aware that many valves have minimum pressure ratings as well-you must have at least a specific amount of pressure for the valve to operate correctly. This is most common in low-power pilot valves. For these valves, air pressure is used to create movement in the valve. Without this minimum pressure, the valve can be energized, but nothing will happen. If a minimum pressure is not specified, the application should be checked to ensure that the minimum system pressure will not fall below the solenoid valve’s rated minimum pressure.


ATMOSPHERE

Atmosphere encompasses a few areas critical to valve selection. These areas are ambient temperature, ingress protection and environment.

Ambient temperature ratings really need close attention to maximize the life of the solenoid valve. The minimum temperature rating depends on the mechanical operation of the valve as far as what elastomers are used in static and dynamic sealing areas. The maximum temperature rating of a solenoid valve is usually limited by the coil. The higher the ambient temperature, the more difficult it is for the coil to dissipate heat, and the more inefficient the coil becomes. Remember that temperature of the media will affect the heat dissipation ability of the coil as well.

Ingress protection is a term that defines a coil's ability to withstand external ingression of dust and water. The most common coil ingress protection rating is Type 4, 4X in North America or

IP-65 in Europe. Type 4, 4X means the coil or coil enclosure is watertight, dust-tight and corrosion-resistant. IP-65 means dust-tight and able to withstand 6.3 mm nozzle water jets from any direction. These ratings are given not only to coils, but to electrical enclosures.

A common mistake in solenoid specifications is choosing an internal elastomer based on external environmental conditions. Most of the time, a valve’s elastomers are internal only and are only affected by the media inside the valve. In other words, if 316L stainless steel is chosen for a valve in a salt-laden environment, choosing a fluoropolymer elastomer when the valve is used for instrument air may not be needed. The fluoropolymer might typically be specified because of a user’s perceptions regarding corrosion resistance, but it might be an unnecessary expense.

Environment can also mean media in the atmosphere such as acetylene that may cause an explosion if ignited by a spark or heat. This area could be addressed in an entirely different article because hazardous environment requirements are truly a place where “the devil is in the details.” An abridged version is given in Table 1.

There are so many nuances and details in making sure the correct agency approvals are obtained that even the most experienced people make mistakes. Such decisions, however, are usually part of the user specification. The plant in which the user is installing the equipment will already have received designations of the required approvals and methods of protection. Some users have multiple areas designated within each plant with different approval requirements depending on the media that could or would be present in those areas of the plant. These decisions have to be made when the plant is designed, and they are reviewed by the appropriate safety officials and insurance companies. However, hazardous environment considerations are an area of major expense for end users and for solenoid manufacturers. The initial cost to get approvals is just the beginning of that cost. Next come regular plant inspections, file fees and paperwork change charges.


VOLTAGE

Voltage is a simple, but still vital part of the specification process. It merely is the voltage of the system to which the valve is wired. Most coils are designed per UL requirements to operate at +10% to -15% of the rated voltage because of normal voltage fluctuations in the line or from the source. However, care is needed with voltage range tolerances, because all coils are not designed this way. The information needed to determine coil design is in the valve manufacturer's installation and maintenance sheets or catalog information. When specifying voltage do not assume that the manufacturer knows whether voltage requirements are AC or DC. When specifying DC voltage, the letters DC should be written out after the voltage value: as in 24/DC. When specifying AC voltage, the frequency should be included (For example: 120/60 or 230/50).


EXTRAS

Many areas must be considered when selecting solenoid valves. A catalog cannot answer all the questions because there are many optional features that may not be included. To be sure the right valve is selected, list specific considerations along with quantities and needed lead times. What is not optional needs to be outlined. If some flexibility in the specification exists, options can be recommended, which is especially helpful when lead times are crucial. A good technical support representative can not only find a valve that meets specification needs, but be able to find one that can be delivered in desired time frames.


Bill Reeson is a technical support manager at Emerson Industrial Automation, ASCO Numatics (www.ASCONumatics.com). Reach him at Bill.Reeson@Emerson.com.

RELATED CONTENT

  • Rigging and Lifting of Large Valves

    This article outlines the challenges of lifting large valve assemblies weighing several tons and illustrates the industrial rigging equipment and lifting operations typically used for these valves.

  • The Rationale Behind Valve Characteristics

    Back in the “early days,” we were taught that, to properly control flow, we should select a linear valve characteristic when the valve controls more than 25% of the piping system pressure drop at full flow.

  • Solenoid Valves: Direct Acting vs. Pilot-Operated

    While presenting in a recent VMA Valve Basics 101 Course in Houston, I found myself in a familiar role: explaining solenoid valves (SOVs) to attendees. (I work with solenoids so much that one VMA member at that conference joked that I needed to be wearing an I Heart Solenoids t-shirt). During the hands-on “petting zoo” portion of the program, which involves smaller groups of attendees, one of the most frequently asked questions I get from people came up: What’s the difference between direct-acting and pilot-operated SOVs, and how do we make a choice?