Water Hammer—Check It Out

Have you ever been in an area of the plant that had just shut down a pump, only to hear an explosive sound a few seconds later?
#gate-globe-check #water-wastewater

Share

Multiple pump systems often use a check valve located between the pump and the discharge header. The purpose of this valve is to prevent backflow from the header to the pump when it is not running. Without the check valve the pump could actually spin backwards.

Depending on the system pressure, these valves can close with such force that they damage the check valve, the pump, and over time even the pump base. Most check valves require reverse flow to close the valve and once this flow momentum has started, it does not stop as quickly as the check valve closes. The result is water hammer, a very destructive force. According to Webster's: Water hammer: a concussion, or sound of concussion, of moving water against the sides of a containing pipe or vessel.

We have seen many plants overcome these laws of physics with the use of an "auto check," also known as a "butterfly check." This concept utilizes a pneumatic-operated butterfly valve, and relatively simple control logic in order to close the valve automatically, prior to shutting down the pump. This action avoids reverse flow, so that the back flow and water hammer never have the chance to develop.

The valves for these applications are typically high-performance butterfly valves with a pneumatic actuator. Accessories include a limit switch and four-way pilot solenoid with two adjustable speed controls. The speed controls restrict the airflow out of the cylinder in both directions, thus regulating the opening and closing speed of the valve.

Control logic for the auto check is simple. When the pump is not pumping, the butterfly valve is closed. When the motor start command is received, either locally or from the PLC, the pump motor is energized. Pressure builds up on the pump side of the auto check valve. A differential pressure switch senses pressure differential between the newly started pump and the header past the auto check. At some predetermined point-such as 1 psi, .5 psi. or .25 psi-the delta p switch makes contact on pressure increase. The switch is sealed in by a relay and energizes the solenoid valve, which opens the butterfly valve smoothly, aided in part by the speed control valves. When the butterfly valve is totally open, a limit switch is tripped and sends a valve-open status to the PLC.

When the motor stop command is received, the pilot solenoid is de-energized and the valve closes at a controlled rate, again aided by the speed controls. When the valve is completely closed the limit switch is tripped, which in turn shuts off the pump motor. This action eliminates water hammer by preventing any back flow from occurring.

BRUCE FENWICK is in technical sales for McJunkin Corporation, Harvey IL. Reach him via 708.225.3120 or at bfenwick@mcjunkin.com.

RELATED CONTENT

  • New Requirements for Actuator Sizing

    After decades of confusion, the American Water Works Association has created new standards for actuator sizing that clear up some of the confusion and also provide guidance on where safety factors need to be applied.

  • Ancient Roman Valves

    The story of water supply in the ancient Roman Empire is grand.

  • Knifegate Valve Maintenance and Repair

    Knife gate valves are used to provide isolation in various applications including oil sands slurries, pulp stock, waste water and power generation.